Product details
Standard 2U body thickness, 19-inch panel, light weight and small size; high reliability, each unit works independently, any output of AC main circuit, bypass, and DC can be load output when it is normal; AC and DC internal electrical isolation, No need for external isolation transformer; mature and reliable active power factor correction technology, power factor 0.99; advanced digital control technology, fast response to external changes, low total voltage distortion, real-time high-quality AC output; high conversion efficiency, AC, DC input peak efficiency is greater than 90%; good electromagnetic compatibility performance, meet GB/T 7260.2-2009 uninterruptible power supply equipment (UPS) electromagnetic compatibility requirements; friendly man-machine interface, simple operation, rich functions, real-time query of various items parameters; provide RS485 communication interface and 6 groups of passive normally open dry contacts, which is convenient for real-time management and monitoring of monitoring software.
★Weight: 13.8Kg
★Size: 448mm*85mm*420mm (W*H*D)
★Cooling method: air cooling
★Working temperature: -10℃~40℃
★AC input voltage VAC: 187 ~ 264
★DC input voltage VDC: 176 ~ 286
★AC output voltage VAC: 220±2%
★Inverter output frequency HZ: 50±0.2
★Output power: resistive load: 4KW; nonlinear load (PF=0.8): 5KVA
★Crest factor: 3:1
★Power factor: 0.8
★Efficiency : ≥ 90%
★Regulation accuracy: ≤ ±3%
★Dynamic voltage transient range: ±5%
★Transient response recovery time: ≤ 10mS
★Synchronization accuracy: ±2%
★Voltage waveform distortion (UTHD): ≤ 3%
★Overload capacity: 105%-125% 10min to bypass; 125%-150% 1min to bypass; > 150% to bypass immediately
★Backwater ripple voltage: ≤ 0.5%
★Total switching time: AC power supply <=> DC power supply: 0mS Bypass output <=> Inverter output: ≤ 4mS
★Noise: half load ≤ 60dB, full load ≤ 65dB
★Communication method: RS485